300-11. Securing & Supporting
A) Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place. Support wires that do not provide secure support shall not be permitted as the sole support.
1) Wiring located above a fire-rated floor/ceiling or roof/ceiling assembly shall not be secured to, or supported by, the ceiling assembly, including the ceiling support wires. An independent means of secure support shall be provided.
2) Wiring located above a non-fire-rated floor/ ceiling or roof/ceiling assembly shall not be secured to, or supported by, the ceiling assembly, including the ceiling support wires. An independent means of secure support shall be provided. Cables and raceways shall not be permitted to be supported by ceiling grids.